IP code
View on Wikipedia

- IP = Ingress Protection
- 2 = number from 0 to 6, or X
- 3 = number from 0 to 9, or X
- C = (optional) letter A, B, C or D
- H = (optional) letter H, M, S or W


The IP code or Ingress Protection code indicates how well a device is protected against water and dust. It is defined by the International Electrotechnical Commission (IEC) under the international standard IEC 60529[1] which classifies and provides a guideline to the degree of protection provided by mechanical casings and electrical enclosures against intrusion, dust, accidental contact, and water. It is published in the European Union by the European Committee for Electrotechnical Standardization (CENELEC) as EN 60529.
The standard aims to provide users more detailed information than vague marketing terms such as waterproof. For example, a cellular phone rated at IP67 is "dust resistant" and can be "immersed in 1 meter of freshwater for up to 30 minutes". Similarly, an electrical socket rated IP22 is protected against insertion of fingers and will not become unsafe during a specified test in which it is exposed to vertically or nearly vertically dripping water. IP22 or IP2X are typical minimum requirements for the design of electrical accessories for indoor use.[2]
The digits indicate conformity with the conditions summarized in the tables below. The digit 0 is used where no protection is provided. The digit is replaced with the letter X when insufficient data has been gathered to assign a protection level. The device can become less capable; however, it cannot become unsafe.
There are no hyphens in a standard IP code. IPX-8 (for example) is thus an invalid IP code.[3]
Etymology
[edit]In the original IEC 60529 standard from year 1976, the letters IP are used without providing an explanation, and referred as "characteristic letters".[4] In the next editions of the standard, from years 1989 and 1999 respectively, the IP is explained to denote "international protection" on both French and English pages. According to the Finnish national committee of the IEC, one possibility is that the abbreviation is a combination of English word ingress and French word pénétration which stands for ingress, but finding the correct answer would require doing a historical study on the 1970's standardization, which is difficult because the experts preparing the original standards are likely retired or deceased.[5]
Code breakdown
[edit]This table shows what each digit or part of the IP code represents.[6]
| Code letters |
First | Second | Third | Additional | Supplementary |
|---|---|---|---|---|---|
| Solid particle protection | Liquid ingress protection | Mechanical impact resistance | Other protections | ||
| IP | 0–6 or X | 0–9 or X | 0–9 | Letter | Letter |
| By definition | Required | Required | No longer used | Optional | Optional |
First digit: Solid particle protection
[edit]The first digit indicates the level of protection the enclosure provides against access to hazardous parts (e.g., electrical conductors, moving parts) and the ingress of solid foreign objects.[7]
| Level sized | Effective against | Description |
|---|---|---|
| X | Unknown | X means no data is available to specify a protection rating about this criterion. |
| 0 | — | No protection against contact and ingress of objects |
| 1 | > 50 mm 2.0 in |
Any large surface of the body, such as the back of a hand, but no protection against deliberate contact with a body part |
| 2 | > 12.5 mm 0.49 in |
Fingers or similar objects |
| 3 | > 2.5 mm 0.098 in |
Tools, thick wires, etc. |
| 4 | > 1 mm 0.039 in |
Most wires, slender screws, large ants, etc. |
| 5 | Dust protected | Ingress of dust is not entirely prevented, but it must not enter in sufficient quantity to interfere with the safe operation of the equipment. |
| 6 | Dust-tight | No ingress of dust; complete protection against contact (dust-tight). A vacuum must be applied. Test duration of up to 8 hours based on airflow. |
Second digit: Liquid ingress protection
[edit]The second digit indicates the level of protection that the enclosure provides against harmful ingress of water.[3]
The ratings for water ingress are not cumulative beyond IPX6. A device compliant with IPX7 (covering water immersion) is not necessarily compliant with IPX5 or IPX6 (covering exposure to water jets). A device that meets both tests is indicated by listing both tests separated by a slash, e.g. IPX5/IPX7.
| Level | Protection against | Effective against | Details |
|---|---|---|---|
| X | Unknown | — | X means no data is available to specify a protection rating concerning these criteria. |
| 0 | None | — | No protection against ingress of water |
| 1 | Dripping water | Dripping water (vertically falling drops) shall have no unsafe effect on the specimen when mounted upright onto a turntable and rotated at 1 RPM. | Test duration: 10 minutes
Water equivalent to 1 mm (0.039 in) rainfall per minute |
| 2 | Dripping water when tilted at 15° | Vertically dripping water shall have no harmful effect when the enclosure is tilted at an angle of 15° from its normal position. A total of four positions are tested within two axes. | Test duration: 2.5 minutes for every direction of tilt (10 minutes total) Water equivalent to 3 mm (0.12 in) rainfall per minute |
| 3 | Spraying water | Water falling as a spray at any angle up to 60° from the vertical shall have no harmful effect, utilizing either: a) an oscillating fixture, or b) a spray nozzle with a counterbalanced shield.
Test a) is conducted for 5 minutes, then repeated with the specimen rotated horizontally by 90° for the second 5-minute test. Test b) is conducted (with a shield in place) for 5 minutes minimum. |
For a spray nozzle:
Test duration: 1 minute per square meter for at least 5 minutes[8] Water volume: 10 liters per minute (0.037 impgal/s) Pressure: 50–150 kPa (7.3–21.8 psi) For an oscillating tube: Test duration: 10 minutes Water volume: 0.07 liters per minute (0.00026 impgal/s) per hole |
| 4 | Splashing of water | Water splashing against the enclosure from any direction shall have no harmful effect, utilizing either:
a) an oscillating fixture, or b) A spray nozzle with no shield. Test a) is conducted for 10 minutes. b) is conducted (without shield) for 5 minutes minimum. |
Oscillating tube: Test duration: 10 minutes, or spray nozzle (same as IPX3 spray nozzle with the shield removed) |
| 5 | Water jets | Water projected by a nozzle (6.3 mm (0.25 in)) against enclosure from any direction shall have no harmful effects. | Test duration: 1 minute per square meter for at least 3 minutes
Water volume: 12.5 litres per minute Pressure: 30 kPa (4.4 psi) at distance of 3 meters (9.8 ft) |
| 6 | Powerful water jets | Water projected in powerful jets (12.5 mm (0.49 in) nozzle) against the enclosure from any direction shall have no harmful effects. | Test duration: 1 minute per square meter for at least 3 minutes
Water volume: 100 liters per minute (0.37 impgal/s) Pressure: 100 kPa (15 psi) at distance of 3 meters (9.8 ft) |
| 6K | Powerful water jets with increased pressure | Water projected in powerful jets (6.3 mm (0.25 in) nozzle) against the enclosure from any direction, under elevated pressure, shall have no harmful effects. Found in DIN 40050, and not IEC 60529. | Test duration: at least 3 minutes[9] Water volume: 75 liters per minute (0.27 impgal/s) Pressure: 1,000 kPa (150 psi) at distance of 3 meters (9.8 ft) |
| 7 | Immersion, up to 1 meter (3 ft 3 in) depth | Ingress of water in harmful quantity shall not be possible when the enclosure is immersed in water under defined conditions of pressure and time (up to 1 meter (3 ft 3 in) of submersion). | Test duration: 30 minutes.[7]
Tested with the lowest point of the enclosure 1,000 mm (39 in) below the surface of the water, or the highest point 150 mm (5.9 in) below the surface, whichever is deeper. |
| 8 | Immersion, 1 meter (3 ft 3 in) or more depth | The equipment is suitable for continuous immersion in water under conditions which the manufacturer shall specify. However, with certain types of equipment, it can mean that water can enter but only so that it produces no harmful effects. The test depth and duration are expected to be greater than the requirements for IPx7, and other environmental effects may be added, such as temperature cycling before immersion. | Test duration: agreement with the manufacturer
Depth specified by the manufacturer, generally up to 3 meters (9.8 ft) |
| 9 | Powerful high-temperature water jets | Protected against close-range high-pressure, high-temperature spray downs.
Smaller specimens rotate slowly on a turntable from 4 specific angles. Larger specimens are mounted in the intended position when used, no turntable required, and are tested freehand for at least 3 minutes at a distance of 0.15–0.2 meters (5.9 in – 7.9 in). The specific requirements for the test nozzle are shown in figures 7, 8, & 9 of IEC (or EN) 60529. This test is identified as IPx9 in IEC 60529. |
Test duration: Fixture: 30 sec. in each of 4 angles (2 min. total), Freehand: 1 min/m2, 3 min. minimum
Water volume: 14–16 liters per minute (0.051–0.059 impgal/s) Pressure: 8–10 MPa (80–100 bar) at distance of 0.10–0.15 meters (3.9 in – 5.9 in) Water temperature: 80 °C (176 °F) |
(All tests with the letter "K" are defined by ISO 20653 (replacing DIN 40050-9) and are not found in IEC 60529, except for IPx9, which is the same as the IP69K water test.)
Supplementary letter (optional)
[edit]For the protection of equipment specific to:
| Letter | Meaning |
|---|---|
| G | Oil resistant |
| F | Oil resistant |
| H | High voltage apparatus |
| M | Motion during water test |
| S | Stationary during water test |
| W | Weather conditions |
The letter K is specified in ISO 20653 (replacing DIN 40050-9) and not in IEC 60529.
IPx9K and IPx9
[edit]DIN 40050-9 extended the newer IEC 60529 rating system with an IP69K rating for high-pressure, high-temperature wash-down applications.[10] Enclosures conforming with ISO 20653:2013 must be both dust-tight (IP6X) and able to withstand high-pressure and steam cleaning.
The IPx9K standard was originally developed for road vehicles—especially those that need regular intensive cleaning (dump trucks, concrete mixers, etc.)—but it also finds use in other areas, such as food processing machinery and car wash systems. It was superseded by ISO 20653:2013 Road Vehicles-Degrees of protection (IP code),[11] and complemented by the addition of a level 9 water ingress testing to IEC 60529, which includes essentially the same spray test as IPx9K, but also includes, in Figure 10 of the standard, a drawing for a test fixture designed to verify the correct water pressure.
Test setup
[edit]The test specifies a spray nozzle that is fed with 80 °C (176 °F) water at 8–10 MPa (80–100 bar; 1,200–1,500 psi) and a flow rate of 14–16 litres per minute (3.7–4.2 US gal/min). The nozzle is held 10–15 cm from the tested device at angles of 0°, 30°, 60° and 90° for 30 seconds each. The test device sits on a turntable that completes a rotation once every 12 seconds (5 rpm). The IPx9 specification details a freehand method for testing larger specimens that will not fit on a turntable (see table above). The free hand method also requires (at least) one additional minute of spray time (1 min/m2, 3 min. minimum). The test distance also increases to .175 m (0.15–0.2 m per section 14.2.9).
United States (NEMA rating)
[edit]In the U.S., the National Electrical Manufacturers Association defines NEMA enclosure types in NEMA standard number 250. The following table outlines which IEC 60529 IP code each respective NEMA guideline meets. Ratings between the two standards are not directly equivalent: NEMA ratings also require additional product features and tests (such as functionality under icing conditions, enclosures for hazardous areas, knock-outs for cable connections and others) not addressed by IP ratings.
| NEMA enclosure[12] | IP code |
|---|---|
| 1 | IP20 |
| 2 | IP22 |
| 3, 3X, 3S, 3SX | IP55 |
| 3R, 3RX | IP24 |
| 4, 4X | IP44, IP66, IP65 |
| 5 | IP53 |
| 6 | IP67 |
| 6P | IP68 |
| 12, 12K, 13 | IP54 |
See also
[edit]- Appliance classes
- EN 62262 – IK code on resistance to mechanical impacts
- MIL-STD-810
- U.S. Military connector specifications for military equivalents
- Water Resistant mark on wrist watches
References
[edit]- ^ "IEC 60529:1989+AMD1:1999+AMD2:2013 CSV | IEC Webstore | water management, smart city, rural electrification". webstore.iec.ch. Retrieved 8 May 2024.
- ^ "IP Rating - Ingress Protection Explained | Tansun". www.tansun.com. Retrieved 8 May 2024.
- ^ a b Ingress Protection: The System of Tests and Meaning of Codes, archived from the original on 22 May 2013.
- ^ IEC Publication 529: Classification des degrés de protection procurés par les enveloppes – Classification of degrees of protection provided by enclosures (1st ed.). International Electrotechnical Commission. 1976.
- ^ "SESKO: Frequently asked questions (in Finnish)". sesko.fi. Retrieved 22 August 2023.
- ^ Source IEx. "Degrees of Protection" (PDF).
- ^ a b International Electrotechnical Commission (2013). IEC 60529 - Degrees of protection provided by enclosures (IP Code). International standard (2.2 ed.). p. 21. ISBN 9782832210864. OCLC 864643678.
- ^ IEC 60529 2013, p. 27.
- ^ "IEC60529 Comprehensive Waterproof Test Chamber for IPX9K and IPX6K Tests". Pego Electronics (Yi Chun) Company Limited. Retrieved 19 March 2025.
- ^ DIN 40050-9: Straßenfahrzeuge; IP-Schutzarten; Schutz gegen Fremdkörper, Wasser und Berühren; Elektrische Ausrüstung [Road vehicles; degrees of protection (IP-code); protection against foreign objects, water and impact; electrical equipment], May 1993. An English translation of the German original is available from DIN.
- ^ ISO 20653:2013 Road Vehicles-Degrees of protection (IP code) Protection of electrical equipment against foreign objects, water and access
- ^ "NEMA Enclosure Types" (PDF). National Electrical Manufacturers Association. November 2005. pp. 7–9. Archived from the original (PDF) on 10 June 2018. Retrieved 10 January 2017.
External links
[edit]IP code
View on GrokipediaIntroduction and Purpose
Definition and Scope
The IP code, formally known as the Ingress Protection rating system, is an international standard defined in IEC 60529 that classifies the degrees of protection provided by enclosures against the ingress of solid foreign objects and liquids into electrical equipment.[1] It specifies the extent to which an enclosure safeguards its contents from dust, solid particles, and water, thereby ensuring the safety and functionality of internal components under specified environmental conditions.[2] The term "Ingress Protection" derives from its focus on preventing the unwanted entry of solids and liquids that could compromise equipment integrity.[1] The scope of the IP code is limited to enclosures for electrical and electronic devices with a rated voltage not exceeding 72.5 kV, applying specifically to the protection of equipment against solid and liquid ingress, as well as access to hazardous parts by persons.[3] It does not extend to non-electrical enclosures, complete assemblies, or protections beyond the defined tests unless explicitly incorporated in related standards.[4] This standardization ensures consistent evaluation across global applications, such as consumer electronics, industrial machinery, and outdoor lighting fixtures. The IP code is typically represented as an alphanumeric designation, such as IP67, where the first character following "IP" indicates protection against solids (e.g., 6 for dust-tight), and the second indicates protection against liquids (e.g., 7 for temporary immersion up to 1 meter).[1] Optional supplementary letters may denote additional conditions, such as "S" for tests conducted with stationary equipment or "W" for weather-exposed conditions, but the core two-digit format addresses the primary ingress concerns.[2] Standardized by the International Electrotechnical Commission (IEC) with its second edition published in 1989, the IP code has undergone amendments, including a significant update in 2013 that enhanced clarity on test conditions and supplementary codes, along with a 2019 corrigendum for further clarifications.[2] This evolution reflects ongoing refinements to meet diverse environmental challenges while maintaining the standard's foundational principles.[1]Historical Context and Etymology
The IP code, denoting Ingress Protection, was coined by the International Electrotechnical Commission (IEC) in the 1970s to describe the effectiveness of enclosures in preventing the ingress of solid objects and liquids.[1] The term "Ingress Protection" reflects the standard's focus on barrier performance against intrusion, with the letters "IP" serving as characteristic markers without further explicit explanation in the original document.[2] The origins of the IP code trace back to European standardization efforts in the mid-1970s, building on earlier national specifications such as the UK's BS 5490:1977, which classified degrees of protection provided by enclosures for electrical equipment.[5] This was formalized internationally with the first edition of IEC 60529, published in 1976, which consolidated disparate requirements from prior standards for motors and low-voltage switchgear into a unified system.[2] The second edition appeared in 1989, followed by amendments in 1999 and 2013 that refined testing protocols and expanded coverage.[2] These developments informed the broader evolution of enclosure protection standards.[2] Key milestones include the adoption of IEC 60529 by the European Committee for Electrotechnical Standardization (CENELEC) as EN 60529 in 1991, promoting harmonization across Europe and replacing national variants like BS 5490.[6] The standard's scope was further integrated into ISO 20653 (2006) for road vehicle applications, ensuring consistent application in specialized sectors. Evolution continued with updates to supplementary codes, such as the introduction of IP69K in the 1990s via extensions like DIN 40050-9 (1993), addressing high-pressure, high-temperature cleaning needs in industries like food processing, and the 2013 IEC amendment adding IPx9 for similar high-pressure tests.[2] These changes reflected growing industrial demands for robust protection against corrosion, mechanical stress, and harsh cleaning methods.[2]Code Structure
Basic Format and Digits
The Ingress Protection (IP) code, as defined in the IEC 60529 standard, classifies the degree of protection provided by enclosures for electrical equipment against access to hazardous parts, ingress of solid foreign objects, and ingress of water.[2] The basic format comprises the letters "IP" followed by two characteristic numerals, where the first numeral (ranging from 0 to 6) denotes the protection level against solid particles and access, and the second numeral (ranging from 0 to 9) denotes the protection level against liquids, with level 9 added in the 2013 amendment for resistance to high-pressure, high-temperature water jets; each successive numeral represents a higher degree of protection.[4] If testing or specification for one aspect is omitted, the letter "X" substitutes for the corresponding numeral, yielding formats such as IP6X (specified solid protection with unspecified liquid) or IPX7 (unspecified solid with specified liquid); the code cannot consist of standalone numerals without the "IP" prefix.[7] Optional extensions include an additional letter (A, B, C, or D) after the numerals to indicate superior access protection to hazardous parts beyond the first numeral's implication, and a supplementary letter (such as H for high-voltage equipment, M for motion during testing, S for stationary testing, or W for weather exposure) to denote special conditions.[4] To claim compliance, the full IP code must be permanently and legibly marked on the equipment or enclosure in accordance with the relevant product standard, ensuring clear identification of the tested protection levels.[8] While three-digit codes (e.g., IP4X5) were occasionally used in earlier editions for partial ratings including mechanical impact, the third edition of IEC 60529 (2013) eliminated the impact numeral, relegating such assessments to the separate IK code system in IEC 62262.[9] A frequent misunderstanding is that the IP code evaluates resistance to mechanical shock, thermal extremes, or chemical corrosion, but it is limited to ingress and access protections unless supplementary designations are applied.[2]Protection Against Solids
The first characteristic numeral in an IP code, ranging from 0 to 6, specifies the degree of protection provided by an enclosure against the ingress of solid foreign objects and access to hazardous internal parts, as defined in the international standard IEC 60529.[2] This numeral evaluates the enclosure's ability to prevent larger objects from entering, progressing to finer particles like dust, ensuring safety and functionality in various environments.[2] The levels are delineated as follows:| Level | Description | Typical Object Size or Condition |
|---|---|---|
| 0 | No protection against solid objects. | N/A |
| 1 | Protected against solid objects greater than 50 mm, such as a human hand. | >50 mm (e.g., sphere or probe of 50 mm diameter) |
| 2 | Protected against solid objects greater than 12.5 mm, such as fingers. | >12.5 mm (e.g., finger-shaped probe) |
| 3 | Protected against solid objects greater than 2.5 mm, such as tools or thick wires. | >2.5 mm (e.g., probe of 2.5 mm diameter) |
| 4 | Protected against solid objects greater than 1 mm, such as small wires or screws. | >1 mm (e.g., probe of 1 mm diameter) |
| 5 | Dust protected: limited ingress of dust is permitted, but in quantities insufficient to interfere with satisfactory operation. | Dust chamber test allowing no harmful deposits |
| 6 | Dust-tight: no ingress of dust under specified test conditions. | Dust chamber test with no dust entry |
Protection Against Liquids
The second characteristic numeral in an IP code, as specified by the International Electrotechnical Commission (IEC) standard 60529, denotes the level of protection provided by an enclosure against the ingress of water and other non-pressurized liquids.[2] This digit ranges from 0 to 9, with each level corresponding to increasingly stringent test conditions that evaluate whether harmful quantities of liquid can enter the enclosure under simulated environmental exposures.[2] The tests are conducted with the enclosure in its normal operating orientation unless otherwise specified, ensuring the assessment reflects real-world use without compromising internal components.[2] The following table summarizes the protection levels against liquids, including brief descriptions and key test parameters derived from IEC 60529:| Level | Description | Test Conditions |
|---|---|---|
| 0 | No protection against water ingress. | Not applicable; no test required.[2] |
| 1 | Protection against vertically falling drops of water (e.g., condensation). | Equivalent to 1 mm/min precipitation rate for 10 minutes.[2] |
| 2 | Protection against drops falling when the enclosure is tilted up to 15 degrees on either side. | Equivalent to 3 mm/min precipitation rate for 2.5 minutes per tilt direction (four positions total).[2] |
| 3 | Protection against spraying water at an angle up to 60 degrees from vertical. | Approximately 10 L/min flow (spray nozzle method) at 50–150 kPa pressure for at least 5 minutes (1 minute per square meter of horizontal surface area).[12] |
| 4 | Protection against splashing water from any direction. | 10 L/min flow at 50–150 kPa pressure for at least 5 minutes (1 minute per square meter).[12] |
| 5 | Protection against low-pressure water jets from any direction. | 12.5 L/min flow at 30 kPa pressure, nozzle at 3 meters distance, for 3 minutes.[2] |
| 6 | Protection against powerful water jets from any direction. | 100 L/min flow at 100 kPa pressure, nozzle at 3 meters distance, for 3 minutes.[2] |
| 7 | Protection against temporary immersion in water up to 1 meter depth. | Immersion so highest point of enclosure is up to 1 meter below surface for 30 minutes in still, fresh water at normal temperature.[2] |
| 8 | Protection against continuous immersion in water under conditions specified by the manufacturer (typically beyond 1 meter depth). | Manufacturer-defined depth and duration (e.g., greater than 1 meter for extended periods); must be more severe than IPX7.[2] |
| 9 | Protection against high-pressure and high-temperature water jets (close-range). | 14–16 L/min flow at 80–100 bar pressure and 80°C temperature, for 30 seconds at 0.10–0.15 meters distance from multiple angles.[2] |
Supplementary Codes
Supplementary codes in the IP rating system consist of optional letters appended after the two characteristic numerals to provide additional information about specific protections or test conditions beyond the standard protection against solids and liquids. These letters extend the basic IP code format, such as IP67, to indicate specialized requirements, and they are defined primarily in IEC 60529. Unlike the numerical digits, supplementary codes do not follow a numerical scale but use distinct letters to denote particular attributes. They are not mandatory and are included only when relevant to the enclosure's intended use or testing scenario.[2] Common supplementary letters include "H," which denotes protection for high-voltage apparatus, ensuring the enclosure safeguards against electrical hazards in high-voltage environments; "M," indicating that the equipment is in motion during the water ingress test; and "S," signifying that the equipment remains stationary during the test. The letter "W," though rare and used primarily for outdoor equipment, specifies protection under weather conditions, as outlined in related standards like IEC 60694 for high-voltage switchgear. These letters are placed immediately after the numerals, for example, IP67M, and testing for them follows modified procedures tailored to the indicated condition.[2] An important extension is the "K" code, particularly in IPx9K ratings, which indicates resistance to high-pressure, high-temperature water jets and is specified in ISO 20653 for applications in road vehicles and industrial settings. This code tests the enclosure's ability to withstand water at 80°C, pressures of 80–100 bar, and flow rates of 14–16 liters per minute, directed from a nozzle at close range (100–150 mm) across multiple angles. IP69K, for instance, combines the IP69 rating for high-pressure water with the "K" extension, making it suitable for automotive and industrial cleaning processes where equipment undergoes rigorous washdowns. Like other supplementary codes, "K" is optional and requires specific verification, but it lacks a numerical grading system.[14][15]Testing Procedures
General Testing Methods
Testing for IP codes is conducted in controlled laboratory environments using calibrated equipment to ensure reproducibility and accuracy. Enclosures are prepared in their normal operating position and tested without energization unless the standard specifies otherwise for functional verification. The ambient temperature during tests ranges from 15°C to 35°C, with standard atmospheric conditions applied throughout.[16] For protection against solid objects, the first characteristic numeral (1 to 4) is verified using rigid test probes of specified dimensions, such as 50 mm spheres for IP1X or 1 mm wires for IP4X. These probes are applied manually or mechanically in every possible direction without undue force—50 N for IP1X, 10 N for IP2X, 3 N for IP3X, and 1 N for IP4X as per IEC 60529 Table 6—advanced as far as possible without deforming the enclosure until contact with hazardous parts or maximum penetration is achieved; acceptance requires no access to live or dangerous components. For IP5X and IP6X, a dust test employs a test chamber filled with talcum powder dried to less than 0.5% moisture by mass, which passes through a square-mesh sieve having a nominal mesh of 75 μm and wire diameter of 50 μm, at a concentration of 2 kg/m³ of the test chamber volume (not used for more than 20 tests) circulated by an air stream producing an air velocity of 2 m/s ± 0.5 m/s near the enclosure. The enclosure is exposed for 8 hours under a negative internal pressure of 20 Pa to 100 Pa for IP5X (limited dust ingress permitted, not interfering with operation) or without negative internal pressure for IP6X (dust-tight); post-exposure, any ingress is assessed by visual inspection and weighing if necessary to ensure no harmful effects.[16] Liquid ingress protection, corresponding to the second characteristic numeral, uses apparatus simulating environmental exposure at a distance of 2.5 to 3 m from the enclosure unless otherwise noted. For IPX3, an oscillating tube with 0.07 l/min flow per opening sprays water over ±60° from vertical (120° arcs) with oscillations completing 360° in approximately 12 seconds, for a total of 5 minutes; IPX4 employs a ±90° from vertical (180° sweep) with 360° in approximately 15 seconds, for a total of 10 minutes, at the same flow rate. For IPX5 and IPX6, handheld nozzles deliver water jets at 2.5 to 3 m distance: 6.3 mm diameter at 12.5 l/min and 30 kPa for IPX5 (minimum 3 minutes total or 1 minute per m² surface area, all orientations), or 12.5 mm diameter at 100 l/min and 100 kPa for IPX6 (same duration). IPX7 involves immersion in a tank at 0.15 m to 1 m depth for 30 minutes, while IPX8 requires agreed-upon immersion depth and duration beyond 1 m, often continuously.[16] Following each test, enclosures undergo visual and functional inspection to detect ingress. Acceptance criteria stipulate no harmful effects, defined as no impairment to safe operation, no safety hazards from accumulated dust or water, and no dripping or leakage impairing functionality; limited dust ingress is permitted for IP5X provided it does not interfere with the satisfactory functioning of the equipment or cause unsafe conditions. These methods verify the IP code digits by simulating real-world ingress threats under standardized conditions.High-Pressure and Specialized Tests
The IPx9 test, as defined in IEC 60529, evaluates the enclosure's resistance to high-pressure and high-temperature water jets intended to simulate powerful cleaning processes. The procedure involves directing a hot water jet at 80°C, with a pressure of 80-100 bar and a flow rate of 14-16 liters per minute, from a distance of 10-15 cm. For smaller enclosures, the specimen is placed on a turntable rotating at 5 rpm and exposed to jets from four nozzles positioned at 0°, 90°, 180°, and 270°, with each nozzle operating for 30 seconds, totaling 120 seconds of exposure. Larger enclosures are tested freehand, with a minimum duration of 3 minutes or 1 minute per square meter of surface area. This test verifies the device's ability to withstand aggressive cleaning without harmful water ingress.[17] The IPx9K variant, specified in ISO 20653 for road vehicles, builds on the IPx9 method with a more standardized setup to account for mechanical stresses in automotive applications. In this test, the enclosure is fixed on a turntable rotating at 5 rpm, while four nozzles of precise dimensions deliver the same water parameters—80°C temperature, 80-100 bar pressure, and 14-16 l/min flow—from 10-15 cm away, each for 30 seconds in sequence, for a total of 120 seconds. Unlike the general IPx9, the IPx9K includes measurement of water impact force (minimum 80 N) and tolerances for nozzle positioning to ensure consistent high-energy exposure from all directions. This supplementary "K" code denotes the enhanced mechanical action simulation.[18][19] While both tests use identical core parameters for temperature and pressure, the IPx9 in IEC 60529 allows flexibility for freehand application on larger items and focuses on general industrial cleaning resistance, whereas IPx9K in ISO 20653 mandates the rotating enclosure and fixed nozzles for precise, repeatable automotive or food processing scenarios where equipment faces high-pressure washdowns. These tests are particularly relevant for environments requiring robust hygiene, such as food manufacturing plants or vehicle underbodies exposed to decontamination sprays.[20][21] To pass either test, the enclosure must show no ingress of water that could impair functionality, determined through post-test visual inspections for leaks, electrical continuity checks, and operational verification under normal conditions. Failure occurs if water enters and causes visible damage, short circuits, or performance degradation.[22][23]Certification and Compliance
The certification process for IP codes involves independent third-party laboratories conducting tests in accordance with IEC 60529 to verify an enclosure's ingress protection level.[24] Organizations such as TÜV SÜD and Intertek perform these evaluations, simulating environmental conditions to assess protection against solids and liquids, and issue detailed test reports upon successful completion.[25] If the product meets the specified IP rating criteria, the laboratory may also provide a certification mark or certificate, which serves as evidence of compliance for regulatory or market purposes.[9] Marking requirements stipulate that the IP code must be affixed visibly and indelibly to the product or its enclosure to indicate the claimed level of protection.[8] This labeling ensures users and inspectors can readily identify the rating, with the standard recommending placement where it remains legible under normal conditions of use. In some cases, particularly for time-sensitive certifications, the marking may include the date of testing to reflect the validity of the results.[4] Maintaining compliance requires re-testing whenever significant design changes occur that could affect the enclosure's protective properties, such as modifications to seals or materials.[26] International recognition of IP code certifications is facilitated through the IECEE CB Scheme, which allows test reports from accredited bodies to be accepted across participating countries, streamlining global market access for electrical products incorporating IP ratings.[27] In the European Union, compliance with IP codes under EN 60529 is often mandatory for electrical equipment falling within the scope of the Low Voltage Directive (2014/35/EU), as the standard is harmonized and its application presumes conformity with the directive's essential safety requirements.[28] Outside the EU, IP certification is typically voluntary but frequently required by industry specifications, procurement contracts, or regional regulations to ensure product reliability.[29]Comparisons and Equivalents
NEMA Ratings in North America
The National Electrical Manufacturers Association (NEMA) develops enclosure ratings under standard ANSI/NEMA 250 for electrical equipment rated up to 1000 volts, primarily used in non-hazardous and hazardous locations to protect against environmental hazards such as dust, water, corrosion, and oil.[30] These ratings, denoted as NEMA Types (e.g., NEMA 4X), extend beyond mere ingress protection by incorporating requirements for mechanical impact resistance, gasket aging under temperature variations, corrosion resistance (indicated by an "X" suffix), and protection against oil and coolants in specific types like NEMA 13.[30] NEMA defines 13 enclosure types, ranging from Type 1 (basic indoor protection against falling dirt) to Type 13 (indoor protection against dust, dripping water, oil, and coolants), with intermediate types like 3, 4, and 6 addressing outdoor and watertight applications.[30] Unlike the IP code, which focuses solely on protection against solid objects and liquids as per IEC 60529, NEMA ratings include broader performance criteria such as resistance to ice formation, external mechanical forces, and long-term environmental degradation, making direct equivalencies approximate rather than exact.[30] For instance, NEMA Type 4 provides watertight protection equivalent to IP66 but adds tests for hose-directed water and corrosion not specified in IP standards.[30]| IP Code | Approximate NEMA Equivalent | Key Notes |
|---|---|---|
| IP54 | NEMA 3 | Dust-protected and splash-proof; NEMA 3 adds rain and ice resistance.[30] |
| IP66 | NEMA 4 | Dust-tight and powerful water jets; NEMA 4 includes impact and gasket aging tests.[30] |
| IP67 | NEMA 6 | Dust-tight and temporary immersion; NEMA 6 covers hose-downs and submersion up to 1 meter.[30] |