Hubbry Logo
Logarithmic mean temperature differenceLogarithmic mean temperature differenceMain
Open search
Logarithmic mean temperature difference
Community hub
Logarithmic mean temperature difference
logo
7 pages, 0 posts
0 subscribers
Be the first to start a discussion here.
Be the first to start a discussion here.
Logarithmic mean temperature difference
Logarithmic mean temperature difference
from Wikipedia

In thermal engineering, the logarithmic mean temperature difference (LMTD) is used to determine the temperature driving force for heat transfer in flow systems, most notably in heat exchangers. The LMTD is a logarithmic average of the temperature difference between the hot and cold feeds at each end of the double pipe exchanger. For a given heat exchanger with constant area and heat transfer coefficient, the larger the LMTD, the more heat is transferred. The use of the LMTD arises straightforwardly from the analysis of a heat exchanger with constant flow rate and fluid thermal properties.

Definition

[edit]

We assume that a generic heat exchanger has two ends (which we call "A" and "B") at which the hot and cold streams enter or exit on either side; then, the LMTD is defined by the logarithmic mean as follows:

The LMTD illustrated in a countercurrent temperature profile[1]

where ΔTA is the temperature difference between the two streams at end A, and ΔTB is the temperature difference between the two streams at end B. When the two temperature differences are equal, this formula does not directly resolve, so the LMTD is conventionally taken to equal its limit value, which is in this case trivially equal to the two differences.

With this definition, the LMTD can be used to find the exchanged heat in a heat exchanger:

where (in SI units):

Note that estimating the heat transfer coefficient may be quite complicated.

This holds both for cocurrent flow, where the streams enter from the same end, and for countercurrent flow, where they enter from different ends.

In a cross-flow, in which one system, usually the heat sink, has the same nominal temperature at all points on the heat transfer surface, a similar relation between exchanged heat and LMTD holds, but with a correction factor. A correction factor is also required for other more complex geometries, such as a shell and tube exchanger with baffles.

Derivation

[edit]

Assume heat transfer [2] is occurring in a heat exchanger along an axis z, from generic coordinate A to B, between two fluids, identified as 1 and 2, whose temperatures along z are T1(z) and T2(z).

The local exchanged heat flux at z is proportional to the temperature difference:

The heat that leaves the fluids causes a temperature gradient according to Fourier's law:

where ka, kb are the thermal conductivities of the intervening material at points A and B respectively. Summed together, this becomes

where K = ka + kb.

The total exchanged energy is found by integrating the local heat transfer q from A to B:

Notice that BA is clearly the pipe length, which is distance along z, and D is the circumference. Multiplying those gives Ar the heat exchanger area of the pipe, and use this fact:

In both integrals, make a change of variables from z to ΔT:

With the relation for ΔT (equation 1), this becomes

Integration at this point is trivial, and finally gives:

,

from which the definition of LMTD follows.

Assumptions and limitations

[edit]
  • It has been assumed that the rate of change for the temperature of both fluids is proportional to the temperature difference; this assumption is valid for fluids with a constant specific heat, which is a good description of fluids changing temperature over a relatively small range. However, if the specific heat changes, the LMTD approach will no longer be accurate.
  • A particular case for the LMTD are condensers and reboilers, where the latent heat associated to phase change is a special case of the hypothesis. For a condenser, the hot fluid inlet temperature is then equivalent to the hot fluid exit temperature.
  • It has also been assumed that the heat transfer coefficient (\alpha) is constant, and not a function of temperature. If this is not the case, the LMTD approach will again be less valid
  • The LMTD is a steady-state concept, and cannot be used in dynamic analyses. In particular, if the LMTD were to be applied on a transient in which, for a brief time, the temperature difference had different signs on the two sides of the exchanger, the argument to the logarithm function would be negative, which is not allowable.
  • No phase change during heat transfer
  • Changes in kinetic energy and potential energy are neglected

Logarithmic Mean Pressure Difference

[edit]

A related quantity, the logarithmic mean pressure difference or LMPD, is often used in mass transfer for stagnant solvents with dilute solutes to simplify the bulk flow problem.

References

[edit]
Revisions and contributorsEdit on WikipediaRead on Wikipedia
from Grokipedia
The logarithmic mean temperature difference (LMTD) is a logarithmic average of the temperature differences between the hot and fluids at the two ends of a , serving as the driving force for calculating rates in steady-flow systems. It is essential in for analyzing configurations where the temperature difference varies nonlinearly along the exchanger length, providing a more accurate alternative to the when fluid temperatures change significantly. The LMTD is mathematically defined as ΔTlm=ΔT1ΔT2ln(ΔT1/ΔT2)\Delta T_{lm} = \frac{\Delta T_1 - \Delta T_2}{\ln(\Delta T_1 / \Delta T_2)}, where ΔT1\Delta T_1 and ΔT2\Delta T_2 represent the differences between the fluids at the and outlet ends, respectively. This formula derives from integrating the local rate dQ=UdAΔTdQ = U \, dA \, \Delta T over the exchanger area, assuming a constant overall UU and yielding Q=UAΔTlmQ = U A \Delta T_{lm}. For parallel-flow exchangers, ΔT1\Delta T_1 is the difference and ΔT2\Delta T_2 the outlet; in counterflow, the differences are defined at the respective ends where the fluids enter and exit oppositely. Key assumptions underlying the LMTD method include steady-state operation, constant specific heats and thermal properties of the fluids, negligible heat loss to the surroundings, and a constant overall heat transfer coefficient. Limitations arise in multipass or cross-flow designs, where correction factors FF are applied such that the effective mean is FΔTlmF \cdot \Delta T_{lm} (with counterflow LMTD as reference), and it is less suitable when the temperature differences at the two ends are nearly equal, as this leads to an indeterminate form in the formula (though the limiting value equals the arithmetic mean). In practice, LMTD is widely applied in the design and performance evaluation of double-pipe, shell-and-tube, and plate heat exchangers across industries such as power generation, chemical processing, and HVAC systems, often complemented by the effectiveness-NTU method for complex scenarios. The value of LMTD is always less than or equal to the , ensuring conservative estimates of capacity.

Concept and Definition

Definition

The logarithmic mean temperature difference (LMTD), denoted as ΔTlm\Delta T_{lm}, serves as the effective average temperature driving force for in heat exchangers where the temperatures change along the length of the device, with the temperatures varying exponentially along the length of the device due to convective . It represents the logarithmic average of the temperature differences between the hot and cold s at the inlet and outlet ends, providing a more accurate measure than the for processes involving in the temperature profile due to the nature of convective . The standard formula for LMTD is: ΔTlm=ΔT1ΔT2ln(ΔT1ΔT2)\Delta T_{lm} = \frac{\Delta T_1 - \Delta T_2}{\ln \left( \frac{\Delta T_1}{\Delta T_2} \right)} where ΔT1\Delta T_1 and ΔT2\Delta T_2 are the local temperature differences between the and at the two ends of the . This expression arises from integrating the differential equation under steady-state conditions with constant specific heats and heat transfer coefficients. For illustration, consider a parallel-flow heat exchanger with the hot fluid entering at 100°C and exiting at 60°C, and the cold fluid entering at 20°C and exiting at 50°C. The end temperature differences are ΔT1=100C20C=80C\Delta T_1 = 100^\circ \text{C} - 20^\circ \text{C} = 80^\circ \text{C} and ΔT2=60C50C=10C\Delta T_2 = 60^\circ \text{C} - 50^\circ \text{C} = 10^\circ \text{C}. Substituting into the formula yields ΔTlm=(8010)/ln(80/10)33.7C\Delta T_{lm} = (80 - 10) / \ln(80/10) \approx 33.7^\circ \text{C}. In heat transfer calculations, the LMTD is incorporated into the overall energy balance as Q=UAΔTlmQ = U A \Delta T_{lm}, where QQ is the heat transfer rate, UU is the overall heat transfer coefficient, and AA is the surface area, enabling straightforward determination of exchanger size or performance.

Physical Significance

The logarithmic mean difference (LMTD) serves as an effective representation of the average driving force for in processes where the difference between fluids varies exponentially along the flow path, such as in steady-state heat exchangers. This variation arises from the fundamental nature of convective , where the local rate is proportional to the instantaneous difference, leading to an in that difference as heat is exchanged. Unlike simpler averages, the LMTD captures this nonlinear profile accurately, ensuring that the calculated total reflects the integrated effect over the entire length without under- or overestimating the driving force. Graphically, the physical significance of the LMTD is evident in the temperature profiles of heat exchangers, where plots of fluid temperatures versus position or heat transferred reveal a logarithmic in the difference between the hot and streams. The LMTD corresponds geometrically to the equivalent constant temperature difference that would produce the same total area under the actual varying curve when divided by the exchanger length, providing an intuitive measure of the mean driving force. This visualization underscores how the LMTD integrates the diminishing , particularly pronounced in counterflow arrangements where the profiles approach each other asymptotically. In practice, the LMTD enables engineers to directly apply the relation for total rate, Q = U A ΔT_lm, where U is the overall and A is the surface area, simplifying the sizing and performance evaluation of heat exchangers without requiring of differential equations along the flow path. This approach is particularly valuable in workflows, allowing for rapid assessment of required exchanger dimensions based on and outlet conditions. The LMTD is expressed in standard temperature units, such as degrees or , and remains consistent regardless of absolute temperature scale shifts, as the logarithmic form inherently cancels additive constants in the differences.

Mathematical Foundation

Derivation for Steady-State Heat Transfer

The derivation of the logarithmic mean temperature difference (LMTD) begins with the fundamental energy balance for steady-state heat transfer between two fluids in a heat exchanger, assuming no phase changes and negligible heat losses to the surroundings. For an infinitesimal heat transfer element, the heat transfer rate dQdQ from the hot fluid to the cold fluid is given by dQ=m˙hcp,hdThdQ = -\dot{m}_h c_{p,h} dT_h, where m˙h\dot{m}_h is the mass flow rate of the hot fluid, cp,hc_{p,h} is its specific heat capacity, and dThdT_h is the differential temperature change (negative for cooling). Similarly, for the cold fluid, dQ=m˙ccp,cdTcdQ = \dot{m}_c c_{p,c} dT_c, with m˙c\dot{m}_c and cp,cc_{p,c} defined analogously, and dTcdT_c positive for heating. These expressions equate the heat lost by the hot fluid to the heat gained by the cold fluid under steady-state conditions, where fluid properties such as specific heats and the overall heat transfer coefficient UU are constant along the exchanger. The local heat transfer across the exchanger surface is expressed as dQ=UdAΔTdQ = U \, dA \, \Delta T, where dAdA is the differential area and ΔT=ThTc\Delta T = T_h - T_c is the local temperature difference between the fluids. Substituting the energy balance into this yields the differential equation dA=dQUΔTdA = \frac{dQ}{U \Delta T}. To integrate, consider the change in temperature difference: d(ΔT)=dThdTc=dQm˙hcp,hdQm˙ccp,c=dQ(1m˙hcp,h+1m˙ccp,c)d(\Delta T) = dT_h - dT_c = -\frac{dQ}{\dot{m}_h c_{p,h}} - \frac{dQ}{\dot{m}_c c_{p,c}} = -dQ \left( \frac{1}{\dot{m}_h c_{p,h}} + \frac{1}{\dot{m}_c c_{p,c}} \right). Rearranging gives d(ΔT)ΔT=UdAm˙hcp,hUdAm˙ccp,c=U(1Ch+1Cc)dA\frac{d(\Delta T)}{\Delta T} = - \frac{U \, dA}{\dot{m}_h c_{p,h}} - \frac{U \, dA}{\dot{m}_c c_{p,c}} = -U \left( \frac{1}{C_h} + \frac{1}{C_c} \right) dA, where Ch=m˙hcp,hC_h = \dot{m}_h c_{p,h} and Cc=m˙ccp,cC_c = \dot{m}_c c_{p,c} are the heat capacities. Integration from the inlet (ΔT1\Delta T_1, A=0A = 0) to the outlet (ΔT2\Delta T_2, A=AA = A) of the exchanger produces ΔT1ΔT2d(ΔT)ΔT=U(1Ch+1Cc)0AdA\int_{\Delta T_1}^{\Delta T_2} \frac{d(\Delta T)}{\Delta T} = -U \left( \frac{1}{C_h} + \frac{1}{C_c} \right) \int_0^A dA, simplifying to ln(ΔT2ΔT1)=UA(1Ch+1Cc)\ln \left( \frac{\Delta T_2}{\Delta T_1} \right) = -U A \left( \frac{1}{C_h} + \frac{1}{C_c} \right). The total QQ relates to the integrated area via Q=UAΔTmQ = U A \Delta T_m, where ΔTm\Delta T_m is the mean temperature difference. Solving for AA yields A=QUln(ΔT2/ΔT1)ΔT2ΔT1A = \frac{Q}{U} \cdot \frac{\ln(\Delta T_2 / \Delta T_1)}{\Delta T_2 - \Delta T_1}, assuming ΔT1>ΔT2\Delta T_1 > \Delta T_2. Rearranging defines the LMTD as ΔTlm=ΔT1ΔT2ln(ΔT1/ΔT2)\Delta T_{lm} = \frac{\Delta T_1 - \Delta T_2}{\ln(\Delta T_1 / \Delta T_2)}, such that the overall equation becomes Q=UAΔTlmQ = U A \Delta T_{lm}. This form arises directly from the exponential nature of the profiles under the stated assumptions of steady-state operation, constant fluid properties, constant UU, and constant heat capacities without external losses.

General Formula and Variations

The logarithmic mean temperature difference (LMTD), denoted as ΔTlm\Delta T_{lm}, provides the effective temperature driving force for in heat exchangers under steady-state conditions with known inlet and outlet temperatures. For a general counterflow configuration, it is calculated using the inlet and outlet temperatures of the hot fluid (Th1T_{h1} and Th2T_{h2}) and the cold fluid (Tc1T_{c1} and Tc2T_{c2}) as follows: ΔTlm=(Th1Tc2)(Th2Tc1)ln(Th1Tc2Th2Tc1)\Delta T_{lm} = \frac{(T_{h1} - T_{c2}) - (T_{h2} - T_{c1})}{\ln \left( \frac{T_{h1} - T_{c2}}{T_{h2} - T_{c1}} \right)} where ΔT1=Th1Tc2\Delta T_1 = T_{h1} - T_{c2} and ΔT2=Th2Tc1\Delta T_2 = T_{h2} - T_{c1} represent the temperature differences at the two ends of the exchanger. This form arises from integrating the local temperature difference along the heat transfer area, assuming constant overall heat transfer coefficient and specific heats. Variations of the LMTD formula adapt to specific operating conditions, such as when the capacity rates (product of mass flow rate and specific heat) of the two fluids are equal, leading to parallel temperature profiles and a constant ΔT\Delta T along the exchanger. In this balanced case, ΔT1=ΔT2\Delta T_1 = \Delta T_2, and the LMTD simplifies to the arithmetic mean temperature difference, ΔTlm=ΔT1\Delta T_{lm} = \Delta T_1. Another common adaptation occurs when one fluid maintains a constant temperature, as in condensers or evaporators during phase change (e.g., steam condensing or refrigerant evaporating). Here, the formula reduces to: ΔTlm=ΔT1ΔT2ln(ΔT1ΔT2)\Delta T_{lm} = \frac{\Delta T_1 - \Delta T_2}{\ln \left( \frac{\Delta T_1}{\Delta T_2} \right)} with ΔT1\Delta T_1 and ΔT2\Delta T_2 defined relative to the isothermal fluid temperature and the inlet/outlet temperatures of the varying fluid. For numerical computation, the LMTD relies on the natural logarithm, which requires ΔT1ΔT2\Delta T_1 \neq \Delta T_2 to avoid division by zero; however, when ΔT1ΔT2\Delta T_1 \approx \Delta T_2, the expression approaches the arithmetic mean through the limit limΔT2ΔT1ΔTlm=ΔT1\lim_{\Delta T_2 \to \Delta T_1} \Delta T_{lm} = \Delta T_1, ensuring continuity and physical consistency. The LMTD method relates to the effectiveness-NTU (number of transfer units) approach by expressing the heat transfer rate Q=UAΔTlmQ = UA \Delta T_{lm}, where effectiveness ϵ\epsilon can be derived from LMTD for cases with unknown outlet temperatures, though NTU often simplifies iterative calculations.

Applications in Heat Exchangers

Counterflow Configurations

In counterflow heat exchangers, the hot and cold fluids flow in opposite directions, with the hot fluid entering at one end and the cold fluid at the other, thereby maximizing the (LMTD) across the exchanger for specified inlet and outlet temperatures. This opposite-flow arrangement sustains a larger and more uniform along the exchanger length compared to other configurations, enhancing overall performance. The LMTD in counterflow is determined using the general LMTD expression with terminal temperature differences defined as ΔT1=Th,inTc,out\Delta T_1 = T_{h,\text{in}} - T_{c,\text{out}} and ΔT2=Th,outTc,in\Delta T_2 = T_{h,\text{out}} - T_{c,\text{in}}. For instance, consider a counterflow where engine oil enters at 160°C and exits at 100°C while heating from 15°C to 85°C; the resulting LMTD is 79.9°C, but using a correction factor F ≈ 0.87 for the multipass arrangement gives an effective mean of about 70°C, enabling effective of approximately 732 kW with a surface area of about 30 m² assuming a typical overall of 354 W/m²·K. In another representative case involving condensation at 120°C heating from 17°C to 80°C, the LMTD calculates to 66.6°C, compared to an of 71.5°C, underscoring the LMTD's accuracy in accounting for the logarithmic profile and yielding a rate of 474 kW. Counterflow configurations provide superior over parallel flow setups for the same surface area and terminal temperatures, as the LMTD is consistently higher—often by 20–30% in typical operating scenarios—allowing greater rates or reduced exchanger size. This stems from the ability of counterflow to achieve cold fluid outlet temperatures exceeding hot fluid outlet temperatures, maximizing up to unity under balanced flow conditions. Due to these benefits, counterflow designs are preferred in most industrial applications, such as boilers, condensers, and process heaters, where compact size and high thermal performance are critical for energy efficiency and cost-effectiveness.

Parallel Flow Configurations

In parallel flow configurations, the hot and cold fluids enter the heat exchanger at the same end and proceed in the same direction to the outlet. The temperature difference at the inlet is ΔT1=Th,inTc,in\Delta T_1 = T_{h,in} - T_{c,in}, while at the outlet it is ΔT2=Th,outTc,out\Delta T_2 = T_{h,out} - T_{c,out}. This arrangement results in a monotonically decreasing temperature difference along the exchanger length, with ΔT1>ΔT2\Delta T_1 > \Delta T_2 always holding due to the co-directional flow. A key constraint in parallel flow is the absence of temperature cross, meaning the cold fluid outlet temperature cannot exceed the hot fluid outlet temperature, as dictated by the second law of . This limitation prevents achieving the higher rates possible in counterflow setups and caps the overall effectiveness. The LMTD, applied via the standard formula, thus yields a smaller value for equivalent terminal temperatures, necessitating larger surface areas for the same heat duty. For instance, consider a parallel flow exchanger heating air from 0°C to 20°C using hot water from 80°C to 60°C; here, ΔT1=80\Delta T_1 = 80^\circC and ΔT2=40\Delta T_2 = 40^\circC, yielding an LMTD of approximately 57.7°C—lower than the 60°C LMTD for counterflow under the same conditions, highlighting the efficiency gap. Parallel flow designs are selected for their simpler requirements and ease of maintenance, though they offer lower thermal performance than counterflow alternatives. They find application in condensers and within systems, as well as in processes involving viscous fluids where rapid initial heating reduces flow resistance.

Assumptions, Limitations, and Extensions

Key Assumptions

The logarithmic mean temperature difference (LMTD) method for analyzing heat transfer in exchangers is predicated on several foundational assumptions that facilitate the integration of the differential energy balance equations, leading to a closed-form expression for the mean temperature driving force. A primary assumption is that the overall heat transfer coefficient UU is constant throughout the exchanger. This requires that the individual convective heat transfer coefficients, wall conduction resistance, and fouling factors remain uniform, independent of local temperature or flow variations, allowing the heat flux to be directly proportional to the local temperature difference. The specific heats cpc_p of both fluids are assumed to be constant, implying that thermophysical properties such as and do not vary significantly across the operating temperature range, which simplifies the energy balance to linear relations between and temperature change. No heat losses to the surroundings are considered, ensuring that the heat exchanger is perfectly insulated and all released by the hot fluid is absorbed by the cold fluid, with no external dissipation or generation. Axial conduction along the flow direction is neglected, meaning is dominated by between the fluids and conduction across the separating wall, without significant longitudinal that could alter the profiles. The operation is steady-state, with constant mass flow rates and no transient effects; additionally, changes in kinetic and of the fluids are deemed negligible compared to the changes due to . These assumptions result in linear temperature profiles for each along the exchanger, derived from the first-law balance under constant capacity rates m˙cp\dot{m} c_p. The flow is modeled as one-dimensional, averaging properties over the cross-section and ignoring radial or circumferential variations. Phase changes in the fluids are excluded unless explicitly specified, as they would violate the constant cpc_p condition and require alternative formulations. Collectively, these assumptions ensure the mathematical tractability of the LMTD approach, though deviations can affect prediction accuracy.

Limitations and Special Cases

In counterflow heat exchangers, the LMTD becomes undefined when a temperature cross occurs, meaning the outlet of the cold exceeds that of the hot , resulting in temperature differences of opposite signs at the ends (ΔT₁ and ΔT₂). This condition leads to a logarithm of a negative or zero value in the LMTD formula, rendering it mathematically invalid. In such cases, alternative methods like of the differential equation or the effectiveness-NTU (ε-NTU) method are employed to accurately predict performance, as these approaches handle the non-monotonic profiles without relying on endpoint differences. The standard LMTD method assumes constant fluid properties, such as (c_p) and (U), but significant variations with temperature—common in high-temperature or viscous flows—can introduce errors. When properties vary, the method over- or underestimates rates, necessitating segmented LMTD approaches where the exchanger is divided into multiple zones with locally evaluated properties and LMTDs summed accordingly. For more pronounced variations, full simulations using or volume-averaging techniques provide precise solutions by resolving property gradients spatially. For multi-pass heat exchangers, such as 1-2 or 2-4 shell-and-tube configurations, the flow arrangement deviates from pure counterflow, reducing the effective temperature driving force; thus, the LMTD for counterflow must be multiplied by a correction factor F (typically 0.6–1.0) derived from configuration-specific charts. These charts, originally developed for common geometries, account for the mixed parallel and counterflow effects, ensuring the heat transfer rate Q = U A F ΔT_{lm} remains accurate. In heat exchangers involving phase changes, like condensers or , the LMTD remains applicable when one fluid stream is isothermal (constant temperature during ), simplifying the calculation as the temperature difference varies linearly along the length. However, if U varies due to changing phase fractions or non-uniform /, adjustments via zone-wise averaging or modified correlations are required to maintain accuracy. Since the early 2000s, advancements have extended beyond analytical LMTD limitations through (CFD) and methods, which model complex geometries, multiphase flows, and transient behaviors in intricate designs like microchannel or compact exchangers. More recent developments as of 2025 include and integration for predictive optimization, additive manufacturing for customized geometries, and advanced to enhance thermal performance in non-ideal conditions.

Comparison with Arithmetic Mean

The arithmetic mean temperature difference (AMTD) is defined as the simple average of the inlet and outlet temperature differences between the two fluids in a , expressed as ΔTam=ΔT1+ΔT22\Delta T_{am} = \frac{\Delta T_1 + \Delta T_2}{2}. This measure is exact only for scenarios where the temperature difference remains constant along the exchanger length, such as during complete or of one fluid. However, in cases with varying temperature profiles, the AMTD overestimates the effective driving force for compared to the LMTD. For example, with ΔT1=100C\Delta T_1 = 100^\circ\mathrm{C} and ΔT2=10C\Delta T_2 = 10^\circ\mathrm{C}, the AMTD yields 55°C, while the LMTD is approximately 39.1°C, representing an overestimation of about 41%; in more extreme imbalances, this error can exceed 50%. Such discrepancies arise because the AMTD assumes a linear temperature variation, ignoring the inherent in counterflow or parallel flow configurations. The AMTD produces negligible error—less than 1%—when ΔT1\Delta T_1 and ΔT2\Delta T_2 differ by no more than 40%, making it suitable for preliminary estimates in nearly scenarios. Prior to Wilhelm Nusselt's introduction of the LMTD method in 1915, practices often relied on the AMTD, which contributed to oversized designs to account for inaccuracies in non-uniform conditions. In general, the LMTD is the preferred approach for accurate unless temperature differences are essentially uniform.

Logarithmic Mean Pressure Difference

The logarithmic mean difference (LMPD) is a logarithmic used to represent the average driving in systems where varies exponentially, analogous in form to the LMTD but applied to gradients. It is defined mathematically as ΔPLM=ΔP1ΔP2ln(ΔP1ΔP2),\Delta P_{\text{LM}} = \frac{\Delta P_1 - \Delta P_2}{\ln \left( \frac{\Delta P_1}{\Delta P_2} \right)}, where ΔP1\Delta P_1 and ΔP2\Delta P_2 represent the pressure differences at the inlet and outlet, respectively. This provides a more accurate average than the arithmetic mean for processes with non-linear pressure decay, such as in flow distribution analysis. The derivation parallels that of LMTD, arising from integrating differential equations assuming steady-state conditions and exponential variations due to or transfer processes. LMPD is primarily applied in specialized contexts within chemical and , such as modeling flow maldistribution in parallel channels of plate heat exchangers and as a driving potential in operations like gas absorption columns. It has seen use since its introduction as a in 2012, particularly for improving accuracy in friction factor calculations under variable flow rates. For instance, in a with an inlet pressure difference of 10 bar and an outlet of 1 bar, the LMPD approximates 3.91 bar, compared to an of 5.5 bar; this illustrates how LMPD captures the effective driving force in decaying profiles. Unlike the LMTD, which is central to analysis, LMPD remains a niche tool, often employed in for dilute solutes in stagnant films or in design for pressure-related flow issues.

References

Add your contribution
Related Hubs
User Avatar
No comments yet.