Hubbry Logo
Fuse (electrical)Fuse (electrical)Main
Open search
Fuse (electrical)
Community hub
Fuse (electrical)
logo
8 pages, 0 posts
0 subscribers
Be the first to start a discussion here.
Be the first to start a discussion here.
Fuse (electrical)
Fuse (electrical)
from Wikipedia
Fuse
A miniature time-delay 250 V fuse that will interrupt a 0.3 A current at after 100 s, or a 15 A current in 0.1 s. 32 mm (1+14 in) long.
Component typePassive
Working principleMelting of internal conductor due to heat generated by excessive current flow
Electronic symbol

Electronic symbols for a fuse

In electronics and electrical engineering, a fuse is an electrical safety device that operates to provide overcurrent protection of an electrical circuit. Its essential component is a metal wire or strip that melts when too much current flows through it, thereby stopping or interrupting the current. It is a sacrificial device; once a fuse has operated, it is an open circuit, and must be replaced or rewired, depending on its type.

Fuses have been used as essential safety devices from the early days of electrical engineering. Today there are thousands of different fuse designs which have specific current and voltage ratings, breaking capacity, and response times, depending on the application. The time and current operating characteristics of fuses are chosen to provide adequate protection without needless interruption. Wiring regulations usually define a maximum fuse current rating for particular circuits. A fuse can be used to mitigate short circuits, overloading, mismatched loads, or device failure. When a damaged live wire makes contact with a metal case that is connected to ground, a short circuit will form and the fuse will melt.

A fuse is an automatic means of removing power from a faulty system, often abbreviated to ADS (automatic disconnection of supply). Circuit breakers have replaced fuses in many contexts, but have significantly different characteristics, and fuses are still used when space, resiliency or cost are significant factors.

History

[edit]

Louis Clément François Breguet recommended the use of reduced-section conductors to protect telegraph stations from lightning strikes; by melting, the smaller wires would protect apparatus and wiring inside the building.[1] A variety of wire or foil fusible elements were in use to protect telegraph cables and lighting installations as early as 1864.[2]

A fuse was patented by Thomas Edison in 1890 as part of his electric distribution system.[3]

Construction

[edit]

A fuse consists of a metal strip or wire fuse element, of small cross-section compared to the circuit conductors, mounted between a pair of electrical terminals, and (usually) enclosed by a non-combustible housing. The fuse is arranged in series to carry all the charge passing through the protected circuit. The resistance of the element generates heat due to the current flow. The size and construction of the element is (empirically) determined so that the heat produced for a normal current does not cause the element to attain a high temperature. If too high of a current flows, the element rises to a higher temperature and either directly melts, or else melts a soldered joint within the fuse, opening the circuit.

The fuse element is made of zinc, copper, silver, aluminium,[citation needed] or alloys among these or other various metals to provide stable and predictable characteristics.[4][5] The fuse ideally would carry its rated current indefinitely, and melt quickly on a small excess. The element must not be damaged by minor harmless surges of current, and must not oxidize or change its behavior after possibly years of service.

The fuse elements may be shaped to increase heating effect. In large fuses, current may be divided between multiple strips of metal. A dual-element fuse may contain a metal strip that melts instantly on a short circuit, and also contain a low-melting solder joint that responds to long-term overload of low values compared to a short circuit. Fuse elements may be supported by steel or nichrome wires, so that no strain is placed on the element, but a spring may be included to increase the speed of parting of the element fragments.

The fuse element may be surrounded by air, or by materials intended to speed the quenching of the arc. Silica sand or non-conducting liquids may be used.

Characteristics

[edit]

Rated current IN

[edit]

A maximum current that the fuse can continuously conduct without interrupting the circuit.

Time vs current characteristics

[edit]

The speed at which a fuse blows depends on how much current flows through it and the material of which the fuse is made. Manufacturers can provide a plot of current vs time, often plotted on logarithmic scales, to characterize the device and to allow comparison with the characteristics of protective devices upstream and downstream of the fuse.

The operating time is not a fixed interval but decreases as the current increases. Fuses are designed to have particular characteristics of operating time compared to current. A standard fuse may require twice its rated current to open in one second, a fast-blow fuse may require twice its rated current to blow in 0.1 seconds, and a slow-blow fuse may require twice its rated current for tens of seconds to blow.

Fuse selection depends on the load's characteristics. Semiconductor devices may use a fast or ultrafast fuse as semiconductor devices heat rapidly when excess current flows. The fastest blowing fuses are designed for the most sensitive electrical equipment, where even a short exposure to an overload current could be damaging. Normal fast-blow fuses are the most general purpose fuses. A time-delay fuse (also known as an anti-surge or slow-blow fuse) is designed to allow a current which is above the rated value of the fuse to flow for a short period of time without the fuse blowing. These types of fuse are used on equipment such as motors, which can draw larger than normal currents for up to several seconds while coming up to speed.

The I2t value

[edit]
Melting fuse on electrical power line pole

The I2t rating is related to the amount of energy let through by the fuse element when it clears the electrical fault. This term is normally used in short circuit conditions and the values are used to perform co-ordination studies in electrical networks. I2t parameters are provided by charts in manufacturer data sheets for each fuse family. For coordination of fuse operation with upstream or downstream devices, both melting I2t and clearing I2t are specified. The melting I2t is proportional to the amount of energy required to begin melting the fuse element. The clearing I2t is proportional to the total energy let through by the fuse when clearing a fault. The energy is mainly dependent on current and time for fuses as well as the available fault level and system voltage. Since the I2t rating of the fuse is proportional to the energy it lets through, it is a measure of the thermal damage from the heat and magnetic forces that will be produced by a fault end.

Breaking capacity

[edit]

The breaking capacity is the maximum current that can safely be interrupted by the fuse. This should be higher than the prospective short-circuit current. Miniature fuses may have an interrupting rating only 10 times their rated current. Fuses for small, low-voltage, usually residential, wiring systems are commonly rated, in North American practice, to interrupt 10,000 amperes. Fuses for commercial or industrial power systems must have higher interrupting ratings, with some low-voltage current-limiting high interrupting fuses rated for 300,000 amperes. Fuses for high-voltage equipment, up to 115,000 volts, are rated by the total apparent power (megavolt-amperes, MVA) of the fault level on the circuit.

Some fuses are designated high rupture capacity (HRC) or high breaking capacity (HBC)[6] and are usually filled with sand or a similar material.[7]

HRC fuse with red blown indication

Low-voltage high rupture capacity (HRC) fuses are used in the area of main distribution boards in low-voltage networks where there is a high prospective short circuit current. They are generally larger than screw-type fuses, and have ferrule cap or blade contacts. High rupture capacity fuses may be rated to interrupt current of 120 kA.

HRC fuses are widely used in industrial installations and are also used in the public power grid, e.g. in transformer stations, main distribution boards, or in building junction boxes and as meter fuses.

In some countries, because of the high fault current available where these fuses are used, local regulations may permit only trained personnel to change these fuses. Some varieties of HRC fuse include special handling features.

Rated voltage

[edit]

The voltage rating of the fuse must be equal to or, greater than, what would become the open-circuit voltage. For example, a glass tube fuse rated at 32 volts would not reliably interrupt current from a voltage source of 120 or 230 V. If a 32 V fuse attempts to interrupt the 120 or 230 V source, an arc may result. Plasma inside the glass tube may continue to conduct current until the current diminishes to the point where the plasma becomes a non-conducting gas. Rated voltage should be higher than the maximum voltage source it would have to disconnect. Connecting fuses in series does not increase the rated voltage of the combination, nor of any one fuse.

Medium-voltage fuses rated for a few thousand volts are never used on low voltage circuits, because of their cost and because they cannot properly clear the circuit when operating at very low voltages.[8]

Voltage drop

[edit]

The manufacturer may specify the voltage drop across the fuse at rated current. There is a direct relationship between a fuse's cold resistance and its voltage drop value.[clarification needed] Once current is applied, resistance and voltage drop of a fuse will constantly grow with the rise of its operating temperature until the fuse finally reaches thermal equilibrium. The voltage drop should be taken into account, particularly when using a fuse in low-voltage applications. Voltage drop often is not significant in more traditional wire type fuses, but can be significant in other technologies such as resettable (PPTC) type fuses.

Temperature derating

[edit]

Ambient temperature will change a fuse's operational parameters. A fuse rated for 1 A at 25 °C may conduct up to 10% or 20% more current at −40 °C and may open at 80% of its rated value at 100 °C. Operating values will vary with each fuse family and are provided in manufacturer data sheets.

Markings

[edit]
A sample of the many markings that can be found on a fuse.

Most fuses are marked on the body or end caps with markings that indicate their ratings. Surface-mount technology "chip type" fuses feature few or no markings, making identification very difficult.

Similar appearing fuses may have significantly different properties, identified by their markings. Fuse markings[9] will generally convey the following information, either explicitly as text, or else implicit with the approval agency marking for a particular type:

Packages and materials

[edit]
Various holders for cartridge ferrule fuses

Fuses come in a vast array of sizes and styles to serve in many applications, manufactured in standardised package layouts to make them easily interchangeable. Fuse bodies may be made of ceramic, glass, plastic, fiberglass, molded mica laminates, or molded compressed fibre depending on application and voltage class.

Cartridge (ferrule) fuses have a cylindrical body terminated with metal end caps. Some cartridge fuses are manufactured with end caps of different sizes to prevent accidental insertion of the wrong fuse rating in a holder, giving them a bottle shape.

Fuses for low voltage power circuits may have bolted blade or tag terminals which are secured by screws to a fuseholder. Some blade-type terminals are held by spring clips. Blade type fuses often require the use of a special purpose extractor tool to remove them from the fuse holder.

Renewable fuses have replaceable fuse elements, allowing the fuse body and terminals to be reused if not damaged after a fuse operation.

Fuses designed for soldering to a printed circuit board have radial or axial wire leads. Surface mount fuses have solder pads instead of leads.

High-voltage fuses of the expulsion type have fiber or glass-reinforced plastic tubes and an open end, and can have the fuse element replaced.

Semi-enclosed fuses are fuse wire carriers in which the fusible wire itself can be replaced. The exact fusing current is not as well controlled as an enclosed fuse, and it is extremely important to use the correct diameter and material when replacing the fuse wire, and for these reasons these fuses are slowly falling from favour.

These are still used in consumer units in some parts of the world, but are becoming less common. While glass fuses have the advantage of a fuse element visible for inspection purposes, they have a low breaking capacity (interrupting rating), which generally restricts them to applications of 15 A or less at 250 VAC. Ceramic fuses have the advantage of a higher breaking capacity, facilitating their use in circuits with higher current and voltage. Filling a fuse body with sand provides additional cooling of the arc and increases the breaking capacity of the fuse. Medium-voltage fuses may have liquid-filled envelopes to assist in the extinguishing of the arc. Some types of distribution switchgear use fuse links immersed in the oil that fills the equipment.

Fuse packages may include a rejection feature such as a pin, slot, or tab, which prevents interchange of otherwise similar appearing fuses. For example, fuse holders for North American class RK fuses have a pin that prevents installation of similar-appearing class H fuses, which have a much lower breaking capacity and a solid blade terminal that lacks the slot of the RK type.

Dimensions

[edit]

Fuses can be built with different sized enclosures to prevent interchange of different ratings of fuse. For example, bottle style fuses distinguish between ratings with different cap diameters. Automotive glass fuses were made in different lengths, to prevent high-rated fuses being installed in a circuit intended for a lower rating.

Special features

[edit]

Glass cartridge and plug fuses allow direct inspection of the fusible element. Other fuses have other indication methods including:

  • Indicating pin or striker pin — extends out of the fuse cap when the element is blown.
  • Indicating disc — a coloured disc (flush mounted in the end cap of the fuse) falls out when the element is blown.
  • Element window — a small window built into the fuse body to provide visual indication of a blown element.
  • External trip indicator — similar function to striker pin, but can be externally attached (using clips) to a compatible fuse.

Some fuses allow a special purpose micro switch or relay unit to be fixed to the fuse body. When the fuse element blows, the indicating pin extends to activate the micro switch or relay, which, in turn, triggers an event.

Some fuses for medium-voltage applications use two or three separate barrels and two or three fuse elements in parallel.

Fuse standards

[edit]

IEC 60269 fuses

[edit]
Cross section of a screw-type fuse holder with Diazed fuse

The International Electrotechnical Commission publishes standard 60269 for low-voltage power fuses. The standard is in four volumes, which describe general requirements, fuses for industrial and commercial applications, fuses for residential applications, and fuses to protect semiconductor devices. The IEC standard unifies several national standards, thereby improving the interchangeability of fuses in international trade. All fuses of different technologies tested to meet IEC standards will have similar time-current characteristics, which simplifies design and maintenance.

UL 248 fuses (North America)

[edit]

In the United States and Canada, low-voltage fuses to 1 kV AC rating are made in accordance with Underwriters Laboratories standard UL 248 or the harmonized Canadian Standards Association standard C22.2 No. 248. This standard applies to fuses rated 1 kV or less, AC or DC, and with breaking capacity up to 200 kA. These fuses are intended for installations following Canadian Electrical Code, Part I (CEC), or the National Electrical Code, NFPA 70 (NEC).

The standard ampere ratings for fuses (and circuit breakers) in USA/Canada are considered 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, and 6000 amperes. Additional standard ampere ratings for fuses are 1, 3, 6, 10, and 601.

UL 248 currently has 19 "parts". UL 248-1 sets the general requirements for fuses, while the latter parts are dedicated to specific fuses sizes (ex: 248-8 for Class J, 248-10 for Class L), or for categories of fuses with unique properties (ex: 248-13 for semiconductor fuses, 248-19 for photovoltaic fuses). The general requirements (248–1) apply except as modified by the supplemental part (240-x). For example, UL 248-19 allows photovoltaic fuses to be rated up to 1500 volts, DC, versus 1000 volts under the general requirements.

IEC and UL nomenclature varies slightly. IEC standards refer to a "fuse" as the assembly of a fusible link and a fuse holder. In North American standards, the fuse is the replaceable portion of the assembly, and a fuse link would be a bare metal element for installation in a fuse.

Automotive fuses

[edit]
Blade type fuses come in six physical sizes: micro2, micro3, low-profile mini, mini, regular and maxi

Automotive fuses are used to protect the wiring and electrical equipment for vehicles. There are several different types of automotive fuses and their usage is dependent upon the specific application, voltage, and current demands of the electrical circuit. Automotive fuses can be mounted in fuse blocks, inline fuse holders, or fuse clips. Some automotive fuses are occasionally used in non-automotive electrical applications. Standards for automotive fuses are published by SAE International (formerly known as the Society of Automotive Engineers).

Automotive fuses can be classified into four distinct categories:

Most automotive fuses rated at 32 volts are used on circuits rated 24 volts DC and below. Some vehicles use a dual 12/42 V DC electrical system[10] that will require a fuse rated at 58 V DC.

High voltage fuses

[edit]
A set of pole-top fusible cutouts with one fuse blown, protecting a transformer - the white tube on the left is hanging down

Fuses are used on power systems up to 115,000 volts AC. High-voltage fuses are used to protect instrument transformers used for electricity metering, or for small power transformers where the expense of a circuit breaker is not warranted. A circuit breaker at 115 kV may cost up to five times as much as a set of power fuses, so the resulting saving can be tens of thousands of dollars.[citation needed]

In medium-voltage distribution systems, a power fuse may be used to protect a transformer serving 1–3 houses. Pole-mounted distribution transformers are nearly always protected by a fusible cutout, which can have the fuse element replaced using live-line maintenance tools.

Medium-voltage fuses are also used to protect motors, capacitor banks and transformers and may be mounted in metal enclosed switchgear, or (rarely in new designs) on open switchboards.

Expulsion fuses

[edit]

Large power fuses use fusible elements made of silver, copper or tin to provide stable and predictable performance. High voltage expulsion fuses surround the fusible link with gas-evolving substances, such as boric acid. When the fuse blows, heat from the arc causes the boric acid to evolve large volumes of gases. The associated high pressure (often greater than 100 atmospheres) and cooling gases rapidly quench the resulting arc. The hot gases are then explosively expelled out of the end(s) of the fuse. Such fuses can only be used outdoors.

A 115 kV high-voltage fuse in a substation near a hydroelectric power plant
Older medium-voltage fuse for a 20 kV network

These type of fuses may have an impact pin to operate a switch mechanism, so that all three phases are interrupted if any one fuse blows.

High-power fuse means that these fuses can interrupt several kiloamperes. Some manufacturers have tested their fuses for up to 63 kA short-circuit current.

Comparison with circuit breakers

[edit]

Fuses have the advantages of often being less costly and simpler than a circuit breaker for similar ratings. The blown fuse must be replaced with a new device which is less convenient than simply resetting a breaker and therefore likely to discourage people from ignoring faults. On the other hand, replacing a fuse without isolating the circuit first (most building wiring designs do not provide individual isolation switches for each fuse) can be dangerous in itself, particularly if the fault is a short circuit.

In terms of protection response time, fuses tend to isolate faults more quickly (depending on their operating time) than circuit breakers. A fuse can clear a fault within a quarter cycle of the fault current, while a circuit breaker may take around half to one cycle to clear the fault. The response time of a fuse can be as fast as 0.002 seconds, whereas a circuit breaker typically responds in the range of 0.02 to 0.05 seconds.

High rupturing capacity fuses can be rated to safely interrupt up to 300,000 amperes at 600 V AC. Special current-limiting fuses are applied ahead of some molded-case breakers to protect the breakers in low-voltage power circuits with high short-circuit levels.

Current-limiting fuses operate so quickly that they limit the total "let-through" energy that passes into the circuit, helping to protect downstream equipment from damage. These fuses open in less than one cycle of the AC power frequency; circuit breakers cannot match this speed.

Some types of circuit breakers must be maintained on a regular basis to ensure their mechanical operation during an interruption. This is not the case with fuses, which rely on melting processes where no mechanical operation is required for the fuse to operate under fault conditions.

In a multi-phase power circuit, if only one fuse opens, the remaining phases will have higher than normal currents, and unbalanced voltages, with possible damage to motors. Fuses only sense overcurrent, or to a degree, over-temperature, and cannot usually be used independently with protective relaying to provide more advanced protective functions, for example, ground fault detection.

Some manufacturers of medium-voltage distribution fuses combine the overcurrent protection characteristics of the fusible element with the flexibility of relay protection by adding a pyrotechnic device to the fuse operated by external protective relays.

For domestic applications, Miniature circuit breakers (MCB) are widely used as an alternative to fuses. Their rated current depend on the load current of the equipment to be protected and the ambient operational temperature. They are available in the following ratings: 6A, 10A, 16A, 20A, 25A, 32A, 45A, 50A, 63A, 80A, 100A, 125A.[11]

Fuse boxes

[edit]

United Kingdom

[edit]

In the UK, older electrical consumer units (also called fuse boxes) are fitted either with semi-enclosed (rewirable) fuses (BS 3036) or cartridge fuses (BS 1361). (Fuse wire is commonly supplied to consumers as short lengths of 5 A-, 15 A- and 30 A-rated wire wound on a piece of cardboard.) Modern consumer units usually contain miniature circuit breakers (MCBs) instead of fuses, though cartridge fuses are sometimes still used, as in some applications MCBs are prone to nuisance tripping.

Renewable fuses (rewirable or cartridge) allow user replacement, but this can be hazardous as it is easy to put a higher-rated or double fuse element (link or wire) into the holder (overfusing), or simply fitting it with copper wire or even a totally different type of conducting object (coins, hairpins, paper clips, nails, etc.) to the existing carrier. One form of fuse box abuse was to put a penny in the socket, which defeated overcurrent protection and resulted in a dangerous condition. Such tampering will not be visible without full inspection of the fuse. Fuse wire was never used in North America for this reason, although renewable fuses continue to be made for distribution boards.

The Wylex standard consumer unit was very popular in the United Kingdom until the wiring regulations started demanding residual-current devices (RCDs) for sockets that could feasibly supply equipment outside the equipotential zone. The design does not allow for fitting of RCDs or RCBOs. Some Wylex standard models were made with an RCD instead of the main switch, but (for consumer units supplying the entire installation) this is no longer compliant with the wiring regulations as alarm systems should not be RCD-protected. There are two styles of fuse base that can be screwed into these units: one designed for rewirable fusewire carriers and one designed for cartridge fuse carriers. Over the years MCBs have been made for both styles of base. In both cases, higher rated carriers had wider pins, so a carrier couldn't be changed for a higher rated one without also changing the base. Cartridge fuse carriers are also now available for DIN-rail enclosures.[12]

North America

[edit]

In North America, fuses were used in buildings wired before 1960. These Edison base fuses would screw into a fuse socket similar to Edison-base incandescent lamps. Ratings were 5, 10, 15, 20, 25, and 30 amperes. To prevent installation of fuses with an excessive current rating, later fuse boxes included rejection features in the fuse-holder socket, commonly known as Rejection Base (Type S fuses) which have smaller diameters that vary depending on the rating of the fuse. This means that fuses can only be replaced by the preset (Type S) fuse rating. This is a North American, tri-national standard (UL 4248–11; CAN/CSA-C22.2 NO. 4248.11-07 (R2012); and, NMX-J-009/4248/11-ANCE). Existing Edison fuse boards can easily be converted to only accept Rejection Base (Type S) fuses, by screwing-in a tamper-proof adapter. This adapter screws into the existing Edison fuse holder, and has a smaller diameter threaded hole to accept the designated Type S rated fuse.[13]

Some companies manufacture resettable miniature thermal circuit breakers, which screw into a fuse socket.[14][15] Some installations use these Edison-base circuit breakers. However, any such breaker sold today does have one flaw. It may be installed in a circuit-breaker box with a door. If so, if the door is closed, the door may hold down the breaker's reset button. While in this state, the breaker is effectively useless: it does not provide any overcurrent protection.[16]

In the 1950s, fuses in new residential or industrial construction for branch circuit protection were superseded by low voltage circuit breakers.

Fuses are widely used for protection of electric motor circuits; for small overloads, the motor protection circuit will open the controlling contactor automatically, and the fuse will only operate for short circuits or extreme overload.

Coordination of fuses in series

[edit]

Where several fuses are connected in series at the various levels of a power distribution system, it is desirable to blow (clear) only the fuse (or other overcurrent device) electrically closest to the fault. This process is called "coordination" and may require the time-current characteristics of two fuses to be plotted on a common current basis. Fuses are selected so that the minor branch fuse disconnects its circuit well before the supplying, feeder fuse starts to melt. In this way, only the faulty circuit is interrupted with minimal disturbance to other circuits fed by a common supplying fuse.

Where the fuses in a system are of similar types, simple rule-of-thumb ratios between ratings of the fuse closest to the load and the next fuse towards the source can be used.

Other circuit protectors

[edit]

Resettable fuses

[edit]

So-called self-resetting fuses use a thermoplastic conductive element known as a polymeric positive temperature coefficient (PPTC) thermistor that impedes the circuit during an overcurrent condition (by increasing device resistance). The PPTC thermistor is self-resetting in that when current is removed, the device will cool and revert to low resistance. These devices are often used in aerospace/nuclear applications where replacement is difficult, or on a computer motherboard so that a shorted mouse or keyboard does not cause motherboard damage.

Thermal fuses

[edit]
Thermal cutoff

A thermal fuse is often found in consumer equipment such as coffee makers, hair dryers or transformers powering small consumer electronics devices. They contain a fusible, temperature-sensitive composition which holds a spring contact mechanism normally closed. When the surrounding temperature gets too high, the composition melts and allows the spring contact mechanism to break the circuit. The device can be used to prevent a fire in a hair dryer for example, by cutting off the power supply to the heater elements when the air flow is interrupted (e.g., the blower motor stops or the air intake becomes accidentally blocked). Thermal fuses are a 'one shot', non-resettable device which must be replaced once they have been activated (blown).

Cable limiter

[edit]

A cable limiter is similar to a fuse but is intended only for protection of low voltage power cables. It is used, for example, in networks where multiple cables may be used in parallel. It is not intended to provide overload protection, but instead protects a cable that is exposed to a short circuit. The characteristics of the limiter are matched to the size of cable so that the limiter clears a fault before the cable insulation is damaged.[17]

Unicode symbol

[edit]

The Unicode character for the fuse's schematic symbol, found in the Miscellaneous Technical block, is U+23DB (⏛).

See also

[edit]

Notes

[edit]

References

[edit]
[edit]
Revisions and contributorsEdit on WikipediaRead on Wikipedia
from Grokipedia
An electrical fuse is a safety device consisting of a thin metal wire or strip enclosed in a non-conductive housing that melts and interrupts the flow of when it exceeds a predetermined threshold, thereby protecting circuits and connected equipment from damage due to overloads or short circuits. Fuses operate on the principle of thermal meltdown, where excessive current generates in the fusible element—typically made of materials like tin, lead, or alloys with low melting points—causing it to sever the circuit before harm occurs to wiring or appliances. Key components include the fusible wire or element, insulating body (often or ), and metal end caps or terminals for connection to the circuit. The first practical electrical fuse was invented by in the 1880s and patented in 1890 as part of his electric distribution system, marking a significant advancement in circuit protection. Early designs evolved from simple melting wires to more reliable forms, with a notable milestone in 1909 when Nicholas J. Conrad and Edmund O. Schweitzer developed the world's first reliable high-voltage power fuse using an arc-extinguishing liquid to enhance performance in power systems. Fuses are essential in residential, industrial, and automotive applications, available in various types such as cartridge, , resettable (PTC), and high-rupturing-capacity (HRC) variants, each suited to specific voltage ratings, current limits, and response speeds to meet standards like those from the (IEC). They remain a cost-effective, one-time-use safeguard, though modern alternatives like circuit breakers offer reusability in some scenarios.

Fundamentals

Definition and Purpose

A fuse is a sacrificial protective device consisting of a calibrated metal wire or strip designed to melt and interrupt the flow of electrical current when it exceeds predetermined safe levels, thereby safeguarding the circuit. This low-resistance component acts as a deliberate weak link in the electrical path, ensuring that excessive current—arising from overloads, short circuits, or faults—triggers a predictable to prevent damage. The primary purpose of a fuse is to protect electrical circuits, connected equipment, and personnel from the hazards of overcurrent by rapidly breaking the circuit and halting current flow, thus minimizing risks of overheating, fire, or equipment failure. Fuses provide reliable, one-time protection that is cost-effective and simple to implement in various applications, from household wiring to industrial systems. The basic operating principle of a fuse relies on the heating effect of current, governed by Joule's law, which states that the heat produced (HH) in a conductor is equal to the square of the current (II), multiplied by the resistance (RR) and time (tt): H=I2RtH = I^2 R t When current surpasses the fuse's rating, this heat generation causes the fusible element to reach its melting point, opening the circuit.

Basic Operation

In normal operation, an electrical fuse functions as a low-resistance conductor connected in series with the circuit, permitting the rated current to flow through it with minimal and generation sufficient only to maintain without damage. The fusible element within the fuse dissipates the produced by the current's resistance, ensuring continuous conduction under designed load conditions. During a fault condition, such as an overload or , the current exceeds the fuse's capacity, generating excessive heat through the resistive effect of the current passing through the fusible element. This causes the temperature of the element to rise rapidly, leading to the initiation of the protective response. The melting process begins as the accumulated heat overcomes the material's , transitioning the solid fusible element from a conductive state to a phase, which physically severs the circuit path and interrupts the current flow. In designs incorporating , any potential electrical arc formed during the interruption is contained and extinguished to prevent re-ignition or damage. This phase change ensures a complete open circuit, halting the fault current effectively. Once operated, the fuse remains in a non-conductive state with the melted element unable to restore continuity, necessitating manual replacement to resume circuit functionality, as fuses lack automatic resetting mechanisms. This one-time sacrificial action underscores the fuse's role as a disposable component.

History

Early Development

The origins of electrical fuses trace back to the mid-19th century, when rudimentary fusible links were employed to safeguard early electrical installations from damage and hazards. These precursors consisted of simple wire or foil elements designed to melt under excessive current, interrupting the circuit to prevent catastrophic failures in systems like telegraph lines and nascent electric setups. As early as 1864, such fusible elements were documented in use for protecting telegraph cables and circuits, marking the initial practical application of overcurrent protection in . The formal invention of the modern electrical fuse is attributed to in the 1890s, who developed it to secure his direct-current electrical distribution systems against faults. In 1890, Edison received U.S. Patent No. 438,305 for a "fuse-block," a device featuring a fusible wire inserted into a block to protect circuits in applications ranging from power distribution to telegraph and lines. This innovation extended to early wire fuses integrated into incandescent lamps, where thin fusible conductors prevented overloads from damaging the filaments or causing fires in Edison's pioneering lighting networks. A notable milestone came in 1909, when Nicholas J. Conrad and Edmund O. Schweitzer developed the world's first reliable high-voltage power fuse, using an arc-extinguishing liquid to improve performance and safety in power distribution systems. Key milestones in the early advanced fuse safety and utility. Enclosed fuses, which contained the fusible element within a protective housing to mitigate arcing and debris, were introduced around , with companies like the D&W Fuse Company (later acquired by ) producing models for electric and power services that met emerging Underwriters Laboratories standards for sizing and ratings. By the , fuses saw adoption in automotive wiring, where glass tube variants protected ignition circuits and electrical accessories from during engine operation, reducing risks in the growing automobile industry. Early fuse designs, particularly open-wire types, presented significant challenges due to their fire risks; the exposed melting wire could ignite nearby combustible materials, exacerbating hazards in wooden structures common at the time. These dangers prompted regulatory pushes in the early , including the establishment of safety standards by organizations like Underwriters Laboratories, which advocated for enclosed constructions to contain arcs and promote safer electrical practices.

Modern Advancements

Following , the electrical fuse industry saw significant standardization efforts in the 1950s, driven by organizations such as the (IEC) and Underwriters Laboratories (UL), which established consistent nomenclature and performance criteria for low-voltage fuses to enhance interoperability and safety in growing electrical systems. This era also marked the introduction of fast-acting fuses, designed to open circuits within seconds to protect sensitive from sudden surges, and time-delay fuses, which tolerate temporary inrush currents while still interrupting faults reliably. These innovations supported the postwar boom in by providing tailored protection against overloads without nuisance tripping. In the 1980s, blade fuses gained widespread popularity in automotive applications due to their compact design, ease of insertion, and color-coding for amperage ratings, replacing earlier glass-tube types in most vehicles produced after 1980. Patented in the , these flat, -shaped fuses offered improved durability and vibration resistance, becoming the standard for protecting automotive circuits amid increasing vehicle . Advancements in materials have focused on specialized alloys to achieve precise melting points, enabling fuses to respond accurately to overcurrent conditions while maintaining stability under normal operation. Environmental regulations further drove innovation, with the European Union's RoHS Directive in restricting hazardous substances like lead in electrical equipment, prompting the development of lead-free and formulations in fuses to comply without compromising performance. Entering the , surface-mount fuses emerged as a key innovation for printed circuit boards (PCBs), offering compact, automated assembly compatibility and high reliability in space-constrained like devices and gear. These chip-style fuses, often in 1206 or smaller packages, provide overcurrent protection with minimal footprint, supporting the trend in PCB design. More recently, smart fuses incorporating visual indicators or (IoT) integration have advanced circuit monitoring, allowing real-time fault detection and remote diagnostics, particularly in electric vehicles (EVs) and as of 2025. In EVs, these fuses enhance battery management by alerting to anomalies, while in renewables, they integrate with smart grids for optimized energy flow. Concurrently, high-breaking-capacity fuses have become essential for solar inverters, capable of interrupting fault currents up to 40,000 amperes at 1,500 V DC to safeguard photovoltaic arrays from arcs and shorts.

Construction

Internal Components

The fusible element serves as the core functional component of an electrical fuse, consisting of a calibrated thin wire, strip, or ribbon engineered to melt precisely when the current surpasses its rated threshold, thereby interrupting the circuit to prevent damage from overcurrent. Common materials for the fusible element include low-melting-point metals and alloys such as tin, copper, silver, zinc, aluminum, lead-tin alloys, or specialized compositions like aluminum-antimony for enhanced performance under specific conditions. These materials are selected for their high electrical conductivity, low resistivity, and predictable melting behavior at temperatures typically ranging from 232°C for tin to higher thresholds for alloys, ensuring reliable operation without excessive voltage drop under normal loads. In designs requiring tolerance to temporary overloads, such as time-delay fuses, the element may adopt a helical or coiled shape to increase surface area for heat dissipation, delaying melting during inrush currents while maintaining responsiveness to sustained faults. The end caps, also known as ferrules in certain configurations, form the conductive terminals at each extremity of the fuse, providing secure electrical and mechanical connections to the circuit. Typically constructed from or for optimal conductivity and durability, these caps are often plated with or tin to resist and improve solderability. The fusible element is firmly attached to the inner surfaces of the end caps via , , or , ensuring low-resistance continuity and structural integrity during normal operation. These components facilitate integration into circuits through methods like clipping into holders, soldering to wires, or blade-style insertion, while insulated variants on higher-current fuses help mitigate accidental contact with live parts. Surrounding the fusible element within the fuse is the filler material, a granular substance critical for safe interruption during fault conditions. Predominantly composed of high-purity , powder, or similar non-conductive media, the filler absorbs released as the element melts, rapidly cooling the molten material and dispersing it to avoid re-ignition. Upon melting, an forms between the separated element segments; the filler quenches this arc by intimately contacting and subdividing it into numerous short arcs, which are extinguished through pressure buildup and insulation formation from fused particles, effectively forcing the current to zero. This arc-quenching action is particularly vital in high-breaking-capacity fuses, where it confines plasma and metal vapors, preventing pressure escalation that could rupture the enclosure. Encasing all internal elements is the fuse body or enclosure, a tubular structure that provides insulation, mechanical protection, and containment of fault byproducts. Constructed from non-conductive materials such as for high-temperature and voltage resilience, for visibility in low-power applications, fiberglass-reinforced or for balanced strength and insulation, or molded for cost-effective general use, the body withstands internal pressures up to several atmospheres during operation. The 's design ensures the arc and molten debris remain isolated, minimizing or risks to surrounding equipment, while its transparency in variants allows of the element's status post-interruption. Sealing between the body and end caps, often via or , maintains environmental integrity against moisture and contaminants.

Materials and Packages

Fuses are enclosed in materials selected for their thermal, electrical, and mechanical properties to ensure safe operation under specified conditions. enclosures are commonly used for high-temperature and high-voltage applications due to their excellent heat resistance and insulating capabilities, capable of withstanding temperatures up to 850°C and voltages exceeding 1000V. housings, often rated UL 94V-0 for retardancy, are preferred for low-voltage fuses, providing lightweight, cost-effective protection in environments below 600V. Glass tubes, prevalent in older designs, offer transparency for of the fusible element, though they are limited to lower voltages around 250V and are less durable against mechanical stress. Various package types accommodate different installation needs and environments. Cartridge fuses feature a cylindrical shape, typically with end caps for or knife-blade contacts, suitable for industrial and panel-mount applications. Blade fuses, with their flat, rectangular profile, are standard in automotive and for easy insertion into fuse blocks. Axial-lead fuses, resembling resistors with wire leads extending from both ends, are designed for through-hole mounting on printed circuit boards (PCBs). Surface-mount device (SMD) fuses, compact and leadless, enable automated assembly directly onto PCB surfaces for high-density . Standard dimensions facilitate interchangeability across manufacturers. Common sizes include the 5x20 mm fuse for and the 1/4" x 1-1/4" (6.3x32 mm) cartridge for general-purpose . Industrial variants often incorporate bolt-on features, with studs or terminals for secure, high-current connections in machinery and power distribution systems. To suit harsh environments, fuse packages incorporate adaptations for against contaminants and compliance with regulations. IP-rated enclosures, such as IP67 for dust-tight and water-immersion resistance, shield against moisture and particulates in outdoor or industrial settings. Halogen-free plastics in modern designs reduce toxic emissions during , aligning with RoHS directives for environmental . These external structures complement internal arc-quenching mechanisms by preventing external factors from compromising performance.

Characteristics

Current and Voltage Ratings

The rated current of an electrical fuse, denoted as INI_N, is the maximum root-mean-square (RMS) current that the fuse can carry continuously under specified ambient conditions, typically 25°C, without melting or opening the circuit. Fuses are manufactured with rated currents spanning a broad range, from fractions of an ampere (e.g., milliamperes for precision applications) to over 1000 A for industrial uses, allowing selection based on circuit requirements. When choosing a fuse, the rated current is generally selected to be 25% to 50% higher than the steady-state load current; this margin accommodates inrush currents, minor overloads, and temperature variations while preventing premature failure or nuisance openings. For instance, a circuit with a 5 A continuous load might use a 6.3 A rated fuse to ensure reliability. The rated voltage of a fuse specifies the highest alternating current (AC) or direct current (DC) system voltage at which the fuse can reliably interrupt an overcurrent, including suppression of the resulting arc to prevent re-ignition or device rupture. Common low-voltage ratings include 250 V AC or 600 V AC, while high-voltage fuses for distribution systems may reach 40 kV or higher, depending on the application. This rating directly influences arc extinction: upon melting, the fuse generates a transient recovery voltage that must exceed the system voltage to quench the plasma arc effectively; inadequate rating leads to sustained arcing, potential explosion, or failure to isolate the fault. DC-rated fuses often require longer designs or special fillers compared to AC equivalents, as the lack of natural zero-crossings in DC prolongs arc persistence, though many fuses carry dual AC/DC ratings up to their specified limit. The fuse's voltage rating must always equal or exceed the circuit's maximum operating voltage to ensure safe operation. The , or interrupting rating, defines the maximum that the fuse can safely interrupt at its rated voltage, preventing explosive failure or fire hazards. Expressed in kiloamperes (kA) RMS symmetrical amperes for AC systems, typical values range from 10 kA for residential applications to 200 kA for high-fault industrial setups, ensuring the fuse clears faults without exceeding its mechanical and thermal limits. This capacity is determined through standardized testing where the fuse must withstand and limit the fault current, with the peak let-through current representing the highest instantaneous value passing through before full interruption. For AC circuits, the breaking capacity accounts for asymmetrical fault conditions, where the peak current can significantly exceed the RMS value due to initial DC offset. To quantify this, the peak asymmetrical short-circuit current IpeakI_{\text{peak}} is calculated from the RMS symmetrical current IrmsI_{\text{rms}} as: Ipeak=2Irms(1+eπ/2)I_{\text{peak}} = \sqrt{2} \cdot I_{\text{rms}} \cdot \left(1 + e^{-\pi / \sqrt{2}}\right)
Add your contribution
Related Hubs
User Avatar
No comments yet.